Vue de la page 0
I2-Thread lead alloy recessed terminal to accept M6/M8 bolt
Polypropylene(UL 94-HB) & Flammability resistance
of (UL 94-V0) can be available upon request.
Cells Per Unit 6
Voltage Per Unit 12
Capacity 100Ah @ 20hr-rate to 1.75V per cell
Weight Approx. 33.5 kg(73.86 lbs)
Maximum Discharge Current 800A(5sec)
Internal Resistance Approx. 3.5 mΩ
Operating Temperature Range
Nominal Operating Temperature Range
Float Charging Voltage
Recommended Maximum Charging 30 A
Current Limit
Equalization and Cycle Service 14.4 to 15.0 VDC/unit Average at
Self Discharge
CSB Batteries can be stored for more than 6 months at
25°C (77°F). Please charge batteries before using . For
higher temperatures the time interval will be shorter.
Terminal
Container Material
Discharge:
Charge:
Storage:
Constant Current Discharge Characteristics Unit:A (25°C,77°F)
GPL 121000
12V 100Ah
Specification
Powered by
GPL 121000 is a general purpose battery up to 10 years in
standby service or more than 260 cycles at 100% discharge in
cycle service . As with all CSB batteries, all are rechargeable ,
highly efficient , leak proof and maintenance free.
13.5 to 13.8 VDC/unit Average at
Width (W)
Dimensions :
Unit: mm (inch)
Overall Height (H) Container height (h) Length (L)
217.6±2.5 (8.57±0.1) 214.6±2.5 (8.45±0.1) 343±2.5 (13.5±0.1) 170±2 (6.69±0.08)
CSB-manufactured
VRLA batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
The system of manufacturer was certified
by TUV CERT according to ISO 9001,ISO 14001.
(http://www.csb-battery.com)
Constant Power Discharge Characteristics Unit:W (25°C,77°F)
@25°C (77°F)
25°C (77°F)
25°C (77°F)
-15°C~50°C ( 5°F~122°F)
-15°C~40°C ( 5°F~104°F)
-15°C~40°C ( 5°F~104°F)
25°C±3°C (77°F±5°F)
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V
423 277 212 127 73.0 52.1 41.1 29.1 18.9 12.2 10.0 5.27
1.67V
375 266 207 125 72.4 51.7 40.7 29.0 18.8 12.1 9.93 5.22
1.70V
355 258 203 124 71.8 51.4 40.6 28.7 18.6 12.0 9.88 5.20
1.75V
317 240 194 120 71.1 50.9 40.2 28.6 18.5 11.9 9.81 5.19
1.80V
283 219 183 115 68.9 49.6 39.3 27.9 18.2 11.8 9.66 5.09
1.85V
245 196 164 106 65.2 47.2 37.6 26.8 17.4 11.4 9.45 4.92
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V
4159 2950 2331 1436 849 610 482 342 223 153 125 63.5
1.67V
4008 2837 2273 1417 843 607 480 340 222 152 124 63.3
1.70V
3863 2772 2252 1404 840 604 478 339 221 151 123 63.2
1.75V
3572 2623 2181 1372 830 599 475 337 220 150 122 62.4
1.80V
3184 2442 2049 1316 809 585 465 331 217 148 121 61.4
1.85V
2769 2227 1856 1234 767 557 444 320 210 142 117 60.0
RA1308
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.
Vue de la page 0
1 2

Résumé du contenu

Page 1 - GPL 121000

I2-Thread lead alloy recessed terminal to accept M6/M8 boltPolypropylene(UL 94-HB) & Flammability resistance of (UL 94-V0) can be available upon

Page 2 - GPL121000

Charge Voltage(V/Cell) Application Temperature Set Point Allowable Range Max.Charge Current Cycle Use 25(77 ) 2.45 2.40~2.50 Standby 25(77 ) 2.275